|
1. What if there is a fluctuation
in steam load?
|
The induction generator (IG) never trips
due to steam load fluctuations unlike an alternator.
The power generator will vary in proportion to the steam
flow rate. If steam flow rate falls below a critical
value (say <20% of the designed value), the IG will
go into the motoring mode. |
| |
| 2. What if there
are fluctuations in inlet steam pressure? |
| Induction generators continue to operate
in spite of large fluctuations in inlet pressure unlike
an alternator. The power generator will vary in proportion
to the pressure at inlet. If it falls below as critical
value (say <50% of designed value), the IG will go
into motoring mode. |
| |
| 3. Can it be used
in parallel with a DG set? |
| It is possible as long as DG governor
is stable and DG power rating is alteast 30% greater than
IG. |
| |
| 4. What is the
break-up of cost of the ECT? |
| Turbine Module |
: |
35% |
| Gear Box Module |
: |
25% |
| Induction Generator |
: |
20% |
| Controls and instrumentation |
: |
10% |
| Mounting skid and miscellaneous |
: |
10% |
|
| |
| 5. How do we control
the power factor? |
| Power factor will be corrected at site
depending upon the client’s existing capacitor bank
and existing power factor. We will provide banks of 10KVAR
and keep adding as necessary at the time of installation,
to bring the PF better than 0.85 lag. |
| |
| 6. Is water quality
a problem? |
| For saturated steam applications, no particular
care is needed as all the dissolved salts will be in the
boiler. If it is good for the boiler, it will be acceptable
for the turbine also. Further since we are using hardened
stainless steel for the turbine, effects of erosion and
corrosion are minimal. In case of super heated steam,
silica content needs to be monitored closely (less than
1 ppm). |
| |
| 7. What is the
life of the turbine? |
| 15 years, since we are using hardened stainless
steel for the turbine rotor. |
| |
| 8. What is the
time between overhauls? |
| It is estimated to be 3 years or more,
with an annual inspection. |
| |
| 9. What is the
life period of the spares and maintenance? |
A. We recommended the following:
Bearing and seals : Annual inspection and change,
if necessary
Lube oil change : Every three years
Some fast moving and low cost spares like oil filters,
gaskets, relays, etc. will be handy and the same will
be advised during installation.
It is advisable to order one set of bearings and seals
along with the turbine.
|
| |
| 10. What is the
life on saturated steam turbines? |
| A. It is expected to be 15 years since
we are using hardened stainless steel for the turbine
rotor. However, adequate care is to be taken to ensure
that only dry steam enters the turbine and this can be
simply accomplished by installing an efficient moisture
separator (with thermodynamic trap) and a Y-strainer in
the inlet line to the turbine. This is not included in
standard scope of supply.
SUPER COOLED VAPOUR:
The steam existing the nozzle will be in a super cooled
state and the passage through the turbine takes less
than a milli-second. It takes about 1 to 2 secs, for
condensation to occur and all the condensation will
occur down stream of turbine, hence it is not harmful
to the turbine. In addition, since it is a hardened
stainless steel blisk, there is no erosion on saturated
steam.
|
| |
| 11. How does an
induction generator work? |
| Whenever an induction motor is run higher
than its synchronous speed by the help of a prime mover
it starts generating power instead of absorbing power.
All induction machines always operate at a lagging power
factor (i.e. the current vector lags the voltage vector
and the cosine of the angle of the lag is defined as the
power factor). The power factor depends on the slip, which
is a function of the loading of the motor. The lag angle
will be 90 deg. when the machine runs at zero slip, that
is at synchronous speed and this is known as quadrature.
At quadrature, it will neither absorb nor generate power.
If with the help of a prime mover such as the angle increases
beyond 90 degrees and the power factor is negative, which
means the machine is generating power. The power factor
is adjusted by adding the required KVAR capacitor bank.
Since the excitation of the IG is from the grid, it
does not require any governing. Grid acts as the governor.
Also it does not call for synchronizing as it automatically
locks itself to the grid. |
| |
| 12. What are the
safety interlocks provided? |
ECT is wired to shut down safely in
any of the following undesirable operating conditions:
- High lube oil temperature
- Low lube oil pressure
- Low air pressure (to valve actuator)
- Over speed (which is unlikely)
- Over voltage
- High winding temperature
- Earth leakage
- Over load
The trip will be annunciated and a hooter will come
‘ON’ and one has to inspect before restarting.
In addition an emergency trip (Mushroom button switch)
is also provided.
|
| |
| 13. What are the
advantages in using high-speed turbines? |
ECT is a high-speed turbine. Following
are the merits:
- For a given enthalpy drop, the turbine diameter
is small
- Hence for a particular mass flow, the arc of steam
admission will be larger
- This results in lower losses caused by partial
admission
- This enhances the adiabatic efficiency of the turbine
- This means higher power for the same steam parameters
|
| |
| 14. What are the
comparisons or differences between alternator and induction
generator? |
Induction generator has the following
advantages:
- IG does not require a governor, the associated
governing valve actuator
- No synchronizing
- No load management is required. No load shedding
under any steam demand condition
- Can accept wide fluctuations in steam flow and
inlet pressure
- Makes most effective use of process steam flow,
maximizes power generation
|
| |
| 15. Can the ECT
take a mechanical drive? |
| It is possible to drive, but would require
a governor to control the speed of the driven equipment.
We will quote on a case-by-case basis. |
| |
| 16. Does a turbine
have reverse power relay? |
| Induction generator does not need a reverse
power relay. Since the chances of going into motoring
mode are so infrequent and as grid power is essential
during starting, reverse power relay is not recommended.
If the client insists, the same can be implemented at
extra cost. Please be advised that this will have to be
bypassed during starting and operational manpower cost
will go up. IG does not require any attention and it is
a ‘ fit and forget’ system. |
| |